Modbus Read, Write and Override Parameters plus Exception Codes
10.7.2 SP
Ramp/Rate/Program
Table 10-10 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Setpoint Ramp/Rate.
Table 10-10 Set-up Group – Setpoint Ramp/Rate
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
SP Ramp
0096 150
INT R/W
0
=
Disabled
1 = Enabled
Single SP Ramp
Time
0019
25
FP
R/W
0 to 255 (minutes)
Final Ramp SP
Value
001A 026
FP
R/W
PV Range in Engineering
Units
SP Rate
00F0 240
INT R/W
0
=
Disabled
1 = Enabled
Rate Up (EU/HR)
006C 108
FP
R/W
0 to 9999
Rate Down
(EU/HR)
006D 109
FP
R/W
0 to 9999
Setpoint
Program
00B2 178
INT R/W
0
=
Disabled
1 = Enabled
Start Segment #
0058
88
FP
R/W
1 to 12
End Segment
#(Soak)
00B0 176
INT
R/W
0 = Soak 2
1 = Soak 4
2 = Soak 6
3 = Soak 8
4 = Soak 10
5 = Soak 12
Engineering Units
or Ramp
Segments
00B6 182
INT
R/W
0 = HRS:MIN
1 = Degrees/Minute
2 = EU/Hour
Program Recycles 0059
89
FP
R/W
0 to 100
Guaranteed Soak
Deviation
0057
087
FP
R/W
0 to 99.9 (0 = no soak)
Program End
State
00B5 181
INT
R/W
0 = Disable SP Program
1 = Hold at Program End
194
UDC3200 Universal Digital Controller Product Manual
12/04