Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Input Algorithm 1
Input A Selection
(used with ID 204
math calculations)
00CD 205
INT
R/W
0 = Input 1
1 = Input 2
2 = Output
Input Algorithm 1
Input B Selection
(used with ID 204
math calculations)
00CE 206
INT R/W
0 = Input 1
1 = Input 2
2 = Output
Input Algorithm 1
Input C Selection
(used with ID 204
math calculations)
00CF 207
INT
R/W
0 = None
1 = Input 1
2 = Input 2
3 = Output
Algorithm1 bias
005C 092
FP
R/W
-999.0 to 9999 in
Engineering Units
Percent Carbon
Value
002E 046
FP
R/W
0.02 to 0.350
Percent Hydrogen 0022
034
FP
R/W
1 to 99 (% H2)
200
UDC3200 Universal Digital Controller Product Manual