Configuration
Function Prompt
Selections or
Parameter
Lower Display
Range of Setting
Upper Display
Definition
LOW VAL
Low Scale Value within
the range of the selected
variable to represent the
minimun output (0 or 4
mA)
AUXILIARY OUTPUT LOW SCALING FACTOR
—
This is a value in engineering units used to
represent all AUX OUT parameters except Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
HIGH VAL
High Scale Value within
the range of the selected
variable to represent the
maximum output (20 mA)
AUXILIARY OUTPUT HIGH SCALING FACTOR
—
This is a value in engineering units used to
represent all AUX OUT parameters except Output.
For Output, this is a value in percent and can be any
value between –5 % and +105 %. However, keep in
mind that relay output types can only be scaled 0 %
to 100 %.
DIG INP1
DIGITAL INPUT 1 SELECTIONS
—All selections are
available for Input 1. The controller returns to its
original state when contact opens, except when
overruled by the keyboard.
NONE
NO DIGITAL INPUT SELECTIONS
TO MAN
TO MANUAL
—Contact closure puts the affected
loop into manual mode. Contact open returns
controller to former mode.
TO LSP
TO LOCAL SETPOINT
—When a remote setpoint is
configured, contact closure puts the controller into
local setpoint 1. When contact opens, the controller
returns to former operation—local or remote
setpoint—unless
SP Select
key is pressed while
digital input is active. If this happens, the controller
will stay in the local setpoint mode when contact
opens.
TO 2SP
TO LOCAL SETPOINT TWO
—Contact closure puts
the controller into local setpoint 2.
TO 3SP
TO LOCAL SETPOINT THREE
—Contact closure
puts the controller into local setpoint 3.
TO DIR
TO DIRECT ACTION
—Contact closure selects
direct controller action.
80
UDC3200 Universal Digital Controller Product Manual
12/04