Modbus Read, Write and Override Parameters plus Exception Codes
10.4 Miscellaneous Read Onlys
10.4.1
Register Addresses for Read Onlys
The identifying register addresses listed in Table 10-3 represent some information that is
Read only. No Writes allowed.
Table 10-3 Miscellaneous Read Onlys
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Software Type
009D 157
INT
RD
READ only (UDC3200)
50 = UDC3200
Software Version 00A7 167
INT
RD
READ only
Value less than 255
10.4.2
SetPoint Program Read Only Information
The identifying register addresses listed in Table 10-4 represent some information for
SetPoint Programming that is Read only. No Writes allowed.
Table 10-4 SetPoint Program Read Only Information
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Present SPP
Segment Number
00FB 251
INT
RD
1 – 12
Segment Time
Remaining in
Minutes
00FC 252
INT
RD
0 – 59 Minutes
Segment Time
Remaining in
Hours
00FD 253
INT
RD
0 – 99 Hours
Cycles Remaining 00FE 254
INT
RD
0 – 100
Current Cycle
Number
00FF 255
INT
RD
0 – 100
188
UDC3200 Universal Digital Controller Product Manual
12/04