Output Calibration
Step
Description
Press
Action
or
until the desired zero value is reached in the upper display.
Upper Display
=
(the desired zero calibration value)
Lower Display
=
ZERO VAL
6 DO
MAN
Set 100 % value
Function
Function
Function
The controller will store the 0 % value and you will see:
Upper Display
=
(the existing span calibration value in counts)
)
Lower Display
=
SPAN VAL
or
until the desired span value is reached in the upper
display.
Upper Display
=
(the desired span calibration value)
Lower Display
=
SPAN VAL
For manual calibration, the motor does not move from its
position prior to the start of Position Proportional
calibration.
7
Exit the Calibration Mode
Function
Function
Function
The controller will store the 100 % value.
Lower
Display
Lower
Display
Lower
Display
or
Setup
Setup
To exit the calibration mode
150
UDC3200 Universal Digital Controller Product Manual
12/04