VISIONPRO
®
8000 WITH REDLINK™
59
68-0312—03
C7189R1004 Wireless Indoor Sensor
Use the following steps to mount the sensor (see Fig. 74):
1.
Remove the wallplate and mount it 4 to 6 feet above the
floor on an interior wall. Drill 3/16-inch holes for drywall,
7/32-inch for plaster.
2.
Attach sensor securely to wallplate as shown.
Fig. 74. Mounting Indoor Sensor.
C7189U1005 Wired Indoor Sensor
Use the following steps to mount the sensor:
1.
Remove the cover from the remote sensor (see Fig. 75).
Fig. 75. Remove the cover.
2.
Pull wires through wire hole.
3.
Position wallplate on wall, level and mark screw hole
positions with pencil.
4.
Drill holes at marked positions, then tap in supplied wall
anchors.
5.
Place wallplate over anchors, insert and tighten mount-
ing screws (see Fig. 76).
Fig. 76. Mount wallplate to wall.
6.
Replace the cover on the remote sensor.
Entry/Exit Remote or Vent Boost Remote
Mounting the remote is optional.
1.
Remove the front cover from the remote.
2.
Use provided screws and wall anchors to fasten the
remote to the wall. Drill 3/16-inch holes for drywall, 7/32-
inch for plaster.
Fig. 77. Mounting Entry/Exit Remote or Vent Boost
Remote.
3.
Replace the cover on the remote.
M24056
M24057
M33095