VISIONPRO
®
8000 WITH REDLINK™
31
68-0312—03
313
Radiant Cycles
Per Hour Stage 1
Note: “Stage 1" is
not displayed if
there is only 1
stage of Radiant
Heat.
1 to 12 CPH
3
Both
No
This ISU is only displayed when ISU 201
Heating Equipment is
Geothermal Radiant
.
The thermostat automatically defaults to the
recommended setting for Geothermal Radiant
Heat (3 CPH).
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
313
Radiant Cycles
Per Hour Stage 2
1 to 12 CPH
3
Both
Yes
This ISU is only displayed when ISU 201
Heating Equipment is
Geothermal Radiant
.
The thermostat automatically defaults to the
recommended setting for Geothermal Radiant
Heat (3 CPH).
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
314
Cool /
Compressor
Cycles Per Hour
Stage 1
Note: “Stage 1" is
not displayed if
there is only 1
stage.
1 to 6 CPH
3
Both
No
This ISU is only displayed when ISU 207 Cool
/ Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
314
Cool /
Compressor
Cycles Per Hour
Stage 2
1 to 6 CPH
3
Both
No
This ISU is only displayed when ISU 207 Cool
/ Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes