VISIONPRO
®
8000 WITH REDLINK™
49
68-0312—03
805
Window
Protection
Off
On
Off
Both
No
Requires an optional outdoor sensor.
Off: The thermostat controls the humidity level
to the user's desired humidity setting. Frost or
condensation may appear on windows.
On: The thermostat prevents frost or
condensation on windows by not allowing the
humidifier to run above a certain level. To
prevent frost or condensation, the thermostat
may turn off the humidifier before the
humidity setting is reached. See “Window
Protection” beginning on page 80.
806
User Humidifier in
Heat Mode
Use Humidifier in
Cool Mode
Use Humidifier in
Off Mode
User Humidifier in Heat Mode - No
or Yes
Use Humidifier in Cool Mode - No
or Yes
Use Humidifier in Off Mode - No
or Yes
User
Humidifier in
Heat Mode -
Yes
Default varies
based on
heating/cooling
equipment
selected
Both
No
Heat: Includes Heat, Emergency Heat and
Auto. If the system is in Auto mode, the
thermostat will allow humidification if the last
call was for heat.
Cool: Includes Cool and Auto. If the system is
in Auto mode, the thermostat will allow
humidification if the last call was for cool. A
discharge air temperature sensor is required
to humidify in the Cool mode.
Off: The thermostat will allow humidification
when the system setting is Off.
See “Set up Humidification” beginning on
807
Humidifier Control
Hum when Heat is On
Hum when Fan is On
Tstat Controls Fan
Hum Controls Fan
Defaults to
Hum when
Heat is On
when ISU 800
Humidifier
Type is Bypass
or Fan Pwrd
Defaults to
Tstat Controls
Fan
when ISU
800 Humidifier
Type is Steam
Both
No
Hum when Heat is On:
The thermostat turns
on the humidifier only if the heat is currently
running and humidification is needed.
Hum when Fan is On
: The thermostat turns
on the humidifier only if the fan is currently
running and humidification is needed.
Tstat Controls Fan
: The thermostat turns on
the humidifier and the fan when
humidification is needed.
Hum Controls Fan
: The thermostat turns on
the humidifier when humidification is needed
and the humidifier controls the fan.
808
Run Humidifier
when Cool is On
Yes
No
Yes
Both
No
Yes: Humidifier can run when the cooling
system is on.
No: Humidifier can NOT run when the cooling
system is on.
810
Hum Tank / Filter
Reminder
Off
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Off
Both
No
This ISU is only displayed if ISU 800
Humidifier Type is Steam.
Run Time Days are not shown if ISU 800
Humidifier Type is set to None.
810
Humidifier Pad
Reminder
Off
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Off
Both
No
This ISU is only displayed if ISU 800
Humidifier Type is Bypass or Fan Pwrd.
Run Time Days are not shown if ISU 800
Humidifier Type is set to None.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes