VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
56
1402
Indoor
Temperature
Offset
-3° F to 3° F (in 1° F increments)
0° F
Both
No
0° F - No difference in displayed temperature
and the actual room temperature.
The thermostat displays up to 3°F (1.5°C)
lower or higher than the actual measured
temperature.
1402
Indoor Humidity
Offset
-12% to 12% (in 1% increments)
0%
Both
No
0% - No difference in displayed humidity and
the actual room humidity.
The thermostat displays up to 12% lower or
higher than the actual measured humidity.
1404
Alert Light
Indicator
On
Off
On
Both
No
The thermostat has a built in light indicator.
When an alert is active, the light will be on
continuous if the thermostat is powered with
24 VAC (C wire) or it will flash if the
thermostat is powered with batteries only. The
light also turns on when the system setting is
set to Em Heat.
Select On to use the light indicator or select
Off to turn off the light.
1500
Dealer Name
[Dealer Name]
None
Both
No
Dealer information is displayed to the user
when an alert is active and the user can
access this information by selecting "Dealer
Information" in the Menu.
1500
Dealer Phone
[Dealer Phone]
None
Both
No
1501
Dealer Email
Address
[Dealer Email Address]
None
Both
No
1501
Dealer Website
[Dealer Website]
None
Both
No
1502
Dealer Message
[Dealer Message]
None
Both
No
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes