VISIONPRO
®
8000 WITH REDLINK™
55
68-0312—03
1014
Vent During Hum
or Dehum Calls
Yes
No
Yes
Both
No
This feature is used to help reach the user's
desired humidity level by not allowing the
ventilation equipment to run during a call for
humidification or dehumidification.
Yes: Ventilation is allowed to run during a call
for humidification or dehumidification.
No: Ventilation is NOT allowed to run during a
call for humidification or dehumidification.
1016
Vent On High
Indoor Humidity
Off
On
On
Both
No
This ISU is only displayed when ISU 1000
Ventilation Type is set to
ERV / HRV
.
Off: The humidity level has no effect on
ventilation.
On: The thermostat removes excess humidity
by turning on the ventilator when the indoor
humidity rises 10% above the user's
humidification setting. The thermostat must
be in the heat mode to ventilate on high
humidity.
1017
Ventilator Core
Reminder
Off
3, 6, 9, 12 Calendar Months
Off
Both
No
Ventilator Core Cleaning Reminder
1017
Ventilator Filter
Reminder
Off
3, 6, 9, 12 Calendar Months
Off
Both
No
Ventilator Filter Cleaning Reminder
1100
Number of UV
Devices
0, 1, 2
0
Both
No
Press the up/down arrows to select the
number of UV devices installed in the system.
Some systems may have two UV devices, one
for the A-Coil and another for Air Treatment. A
replacement reminder can be setup for each
one. Select 0 if no UV devices are installed.
1105
UV Bulb 1
Reminder
Note: “1” is not
displayed if there
is only 1 UV Bulb
Off, 6, 12, 24 Calendar Months
Off
Both
No
UV Bulb 1 Replacement Reminder
1105
UV Bulb 2
Reminder
Off, 6, 12, 24 Calendar Months
Off
Both
No
UV Bulb 2 Replacement Reminder
1200
Custom
Reminders
View / Edit Custom Reminders
Add Custom Reminders
None
Both
No
See “Customizable Reminders” beginning on
28
Backlighting
On Demand
Continuous
On Demand
Both
No
Select Continuous or On Demand
backlighting. Select Continuous backlighting if
you would like the backlight to be on all the
time (C wire is required for Continuous
backlighting).
Select On Demand backlighting if you would
like the backlight to only turn on after a key
press. After you complete your changes, the
screen stays lit for 16 seconds if the
thermostat is battery powered only or it stays
lit for 45 seconds if the thermostat is system
powered (C wire).
1400
Clock Format
12 hour
24 hour
12
Both
No
1401
Daylight Saving
Time
Off
On
On
Both
No
Set to Off in areas that do not follow Daylight
Saving Time.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes