VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
54
1012
Vent Priority
Lockouts
ASHRAE
Lockouts
Residential
No
Lockouts are Priority:
The thermostat places
a priority on lockouts versus the ASHRAE 62.2
ventilation standard. The thermostat will not
run ventilation during the following lockout
conditions (if configured) unless you
manually call for ventilation:
•
Lockout Ventilation during Outdoor Conditions
(ISU 1013)
•
Lockout Ventilation on Humidification or
Dehumidification Calls (ISU 1014)
•
Lockout Ventilation during “Sleep” (Residential)
or “Unoccupied” (Commercial) program
periods. Note: This option is set by the user on
the Ventilation screen in the Menu.
ASHRAE is Priority:
ASHRAE requires
additional ventilation following a long off
cycle. The thermostat meets the ASHRAE 62.2
ventilation standard by running additional
ventilation when outdoor conditions are
favorable. If ASHRAE cannot be met when
outdoor conditions are favorable, the
thermostat will override the outdoor lockouts
and run ventilation. When using this option, it
is recommended to increase the rate (CFM) of
the ventilation equipment to meet the ASHRAE
62.2 ventilation standard in a shorter run time.
Notes:
•
ISU 1014 Lockout Ventilation on Humidification
or Dehumidification calls is not an option when
you select ASHRAE is Priority.
•
The ability to lockout ventilation during the
“Sleep” or Unoccupied program periods is not
an option when you select ASHRAE is Priority.
1013
Low Outdoor
Temp Vent
Lockout
Off
-20° F to 40° F (in 5° F
increments)
Off
Both
No
Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to
ERV / HRV
or
Fresh
Air Damper
.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
1013
High Outdoor
Temp Vent
Lockout
Off
80° F to 110° F (in 5° F
increments)
Off
Both
No
Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to
ERV / HRV
or
Fresh
Air Damper
.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
1013
High Out. Dew
Point Vent
Lockout
Off
65° F to 85° F (in 5° F increments)
Off
Both
No
Requires a Wireless Outdoor Sensor (sense
outdoor humidity).
This ISU is only displayed when ISU 1000
Ventilation Type is set to
ERV / HRV
or
Fresh
Air Damper
.
See “Ventilation — Outdoor Condition
Lockouts (ISU 1013)” beginning on page 91.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes