VISIONPRO
®
8000 WITH REDLINK™
25
68-0312—03
222
A-L/A Terminal
None
Time Of Day
Economizer
Heat Pump Fault
None
Commercial No
This ISU is only displayed when ISU 101
Application is
Commercial
.
Note: When the thermostat is setup for
Residential, the L/A terminal operates as
described under "Heat Pump Fault". The L/A
terminal requires no setup for residential
applications.
None:
The A-L/A terminal is not used.
Time of Day:
The A-L/A terminal is energized
during Occupied periods and when the user
overrides the temperature. The terminal is de-
energized during Unoccupied periods and in
Standby mode.
Economizer:
The thermostat controls an
economizer module to provide ventilation
during Occupied periods and free cooling
when outdoor conditions are favorable. The
A-L/A terminal is energized during Occupied
periods and during a call for cooling in
Unoccupied periods. See “Economizer and
Time of Day (TOD) Operation” beginning on
Notes: The economizer module determines
when outdoor conditions are favorable for free
cooling.
Heat Pump Fault:
When 24 volts is detected
on the L/A terminal (compressor monitor), the
thermostat displays a message to alert the
user when the heat pump requires service.
The L/A terminal sends a continuous output to
a zone panel when the thermostat is set to
Emergency Heat mode. The zone panel will
not turn on the heat pump when a zone is set
to Emergency Heat mode.
300
System
Changeover
Manual
Automatic
Manual:
if ISU 101 is
Residential
Automatic:
if ISU 101 is
Commercial
Both
No
Manual:
The user must select heating or
cooling as needed to maintain the desired
indoor temperature.
Automatic:
The user has the option to select
Auto for the system setting. In Auto mode, the
thermostat controls heating and cooling
equipment as needed to maintain the desired
indoor temperature.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes