VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
40
409
Adaptive Recovery
No
Yes
Yes
Residential
No
No: The system will begin heating or cooling
recovery at the scheduled time.
Yes: The thermostat will begin heating or
cooling recovery early to ensure that the
temperature is reached at the scheduled time.
The thermostat will adjust the start time of the
equipment based on how quickly the
scheduled temperature was reached on
previous days. See page 71 for more
information on Adaptive Intelligent Recovery.
410
Minimum Cool
Setpoint
50° F to 99° F
50° F
Both
No
The user cannot set the temperature below
this level.
410
Maximum Heat
Setpoint
40° F to 90° F
90° F
Both
No
The user cannot set the temperature above
this level.
411
Keypad Lockout
Unlocked
Partially Locked
Fully Locked
Unlocked
Both
No
Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any
settings.
412
Residential:
Entry / Exit
Remote - Home
Cool Setpoint
Commercial:
Entry / Exit
Remote -
Occupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 410.
75° F
Both
No
The thermostat maintains this Cool setting
when the user presses Home / Occupied at the
Entry / Exit Remote. Select
None
to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
412
Residential:
Entry / Exit
Remote - Home
Heat Setpoint
Commercial:
Entry / Exit
Remote -
Occupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 410.
70° F
Both
No
The thermostat maintains this Heat setting
when the user presses Home / Occupied at the
Entry / Exit Remote. Select
None
to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
413
Residential:
Entry / Exit
Remote - Away
Cool Setpoint
Commercial:
Entry / Exit
Remote -
Unoccupied Cool
Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 410.
78° F
Both
No
The thermostat maintains this Cool setting
when the user presses Away / Unoccupied at
the Entry / Exit Remote. Select
None
to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes