VISIONPRO
®
8000 WITH REDLINK™
47
68-0312—03
616
Fan Failure Alert is
[See Settings]
N.O. when Fan Runs
N.C. when Fan Runs
N.C. when Fan
Runs
Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open when Fan is Running: The Dry
Contact device is open when the fan is
running and will close when the fan is not
running.
Normally Closed when Fan is Running: The
Dry Contact device is closed when the fan is
running and will open when the fan is not
running.
617
Custom Alert
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module.
Select the terminals wired to the Custom Dry
Contact Device.
618
Custom Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a problem.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a problem.
619
Custom Alert
Name
View/Edit Custom Alert
View/Edit
Custom Alert
Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Enter a name for the custom alert dry contact.
The thermostat displays this name including a
brief message (entered on the next screen -
ISU 620) when a dry contact device detects a
problem.
620
Cust Alert
Message
View/Edit Custom Alert
View/Edit
Custom Alert
Both
Yes
Dry Contact Alerts require an EIM (Equipment
Interface Module).
Enter a message for the custom alert dry
contact. The thermostat displays this message
when a dry contact device detects a problem.
700
Filter Type
None
Elec. Air Cleaner
Media
Media
Both
No
702
Number of Air
Filters
1 to 2
1
Both
No
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes