VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
44
600
Fan Failure Dry
Contact Alert
No
Yes
No
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
600
Custom Dry
Contact Alert
No
Yes
No
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
601
Remote Setback
None
S1
S2
S3
S4
None
Commercial Yes
Remote Setback requires an Equipment
Interface Module.
Select the terminals wired to the Remote
Setback Dry Contact Device.
602
Remote Setback is
[See Settings]
N.O. when Occupied
N.C. when Occupied
N.O. when
Occupied
Commercial Yes
Remote Setback requires an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open when Occupied: The Dry
Contact device is open when the room is
occupied and will close when the room is
unoccupied.
Normally Closed when Occupied: The Dry
Contact device is closed when the room is
occupied and will open when the room is
unoccupied.
603
Remote Setback
Time Delay
0 to 30 minutes (in 5 minute
increments)
0 minutes
Commercial Yes
Remote Setback requires an EIM (Equipment
Interface Module).
The
Remote Setback Time Delay
forces the
thermostat to wait before it switches from
Occupied to the Remote Setback temperature
settings.
When set to 0 minutes, the thermostat will
switch from Occupied to the Remote Setback
temperature settings immediately when the
room is unoccupied.
604
Remote Setback
Cool Setpoint
72° F to 90° F
85° F
Commercial Yes
Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy
sensor tells the thermostat to go to setback
settings when no one is in the room. If
someone is in the room, then it follows the
settings of the occupied period. The
occupancy sensor is ignored during
unoccupied periods.
If the thermostat is setup for non-
programmable, the occupancy sensor tells the
thermostat to go to setback settings when no
one is in the room. If someone is in the room,
then it follows the settings set by the user.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes