VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
38
407
Min. Cool
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
3° F/hr
Commercial No
Off: The cooling system will begin recovery at
the time that is scheduled.
When a
Minimum Recovery Ramp Rate
is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a
Minimum Recovery Ramp Rate
based
on the rate that the cooling system can
recover at for a hot day in your region. Default
setting is 3° F / hour.
If an outdoor sensor is installed, set an
Outdoor Temperature
that is representative of
a hot day in your region to be associated with
the
Minimum Recovery Ramp Rate
. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature. If there is no outdoor
sensor, the
Minimum Recovery Ramp Rate
is
used.
407
Min. Cool
Recovery Outdoor
Temp
Off
-20° F to 100° F
90° F
Commercial No
Off: The cooling system will begin recovery at
the time that is scheduled.
When a
Minimum Recovery Ramp Rate
is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a
Minimum Recovery Ramp Rate
based
on the rate that the cooling system can
recover at for a hot day in your region. Default
setting is 3° F / hour.
If an outdoor sensor is installed, set an
Outdoor Temperature
that is representative of
a hot day in your region to be associated with
the
Minimum Recovery Ramp Rate
. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature. If there is no outdoor
sensor, the
Minimum Recovery Ramp Rate
is
used.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes