VISIONPRO
®
8000 WITH REDLINK™
68-0312—03
26
300
Auto Changeover
Deadband
2° F to 9° F (in 1° F increments)
3° F
Both
No
This ISU is only displayed when ISU 300 is set
to
Automatic.
Deadband is the minimum separation between
heat and cool settings when the thermostat is
setup for Auto Changeover. For example, if the
deadband is set to 3° F and the cool setpoint
is 75° F, the warmest heat setpoint allowed
would be 72° F. If the heat setpoint is adjusted
above 72° F, it will automatically adjust the
cooling setpoint higher to maintain the 3° F
deadband.
When ISU 907 or ISU 910 (Dehum Over
Cooling Limit) is set to 1, 2, 3, 4 or 5 F, the
thermostat will not show the full Deadband
range. For example, if you set a Deadband of 3
F and an Over Cooling Limit of 2 F, the
minimum Deadband that you can select will
be 5 F. This prevents the heating system from
turning on when the thermostat over cools to
reach the dehumidification setting.
301
Control Options
Basic Options
Advanced Options
Basic Options Both
No
Basic Options:
The Installer Setup displays
basic temperature control options which
include Backup Heat Droop, Backup Heat
Upstage Timer, Outdoor Temperature
Lockouts and Cycle Rate settings per stage.
Note: Outdoor Temperature Lockouts only
apply to Heat Pump applications.
Advanced Options:
The Installer Setup
displays both Basic and Advanced Options.
Advanced temperature control options include
Finish With High Cool Stage, Finish With High
Heat Stage, and Temperature Differential
settings between all stages.
302
Finish With High
Cool Stage
No
Yes
No
Both
No
ISU 301 Control Options must be set to
Advanced
to view or adjust
Finish With High
Cool Stage.
This ISU is only displayed when the
thermostat is set for 2 or more cool stages.
When set to
Yes
, this feature keeps the high
stage of the cooling equipment running until
the desired setpoint is reached.
302
Finish With High
Heat Stage
No
Yes
No
Both
No
ISU 301 Control Options must be set to
Advanced
to view or adjust
Finish With High
Heat Stage.
This ISU is only displayed when the
thermostat is set for 2 or more heat stages.
When set to
Yes
, this feature keeps the high
stage of the heating equipment running until
the desired setpoint is reached.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes