Fig. 64. CH Hydronic Status menu (middle).
Fig. 65. CH Hydronic Status menu (bottom).
The status data in Table 45 displays first when the DHW
Hydronic heating loop is selected on the Home page. Scrolling
through the status groups eventually shows both.
The bar graph displayed for the CH control loop (hydronic) is
the outlet sensor temperature; for the DHW control loop it is
the DHW sensor temperature. When no analog DHW sensor
is installed (digital switch instead), the inlet sensor
temperature is displayed.
Fig. 66. DHW Hydronic Status menu (top).
Fig. 67. DHW Hydronic Status menu (middle).
Table 45. DHW Hydronic Status.
Data Comment
DHW enable
Enabled, Disabled
Demand source
Unknown, No source demand, CH,
DHW, Lead Lag, CH frost protection,
DHW frost protection, No demand due
to burner switch
DHW burner demand On or Off
DHW high limit
Temp setting between -40 °F to 266 °F
(-40 °C to 130 °C)
DHW high limit
setpoint
Temp setting between -40 °F to 266 °F
(-40 °C to 130 °C)
DHW priority override
time
0-600 seconds
DHW pump
On or Off
DHW pump demand On or Off
DHW pump overrun
time
Running overrun time for DHW pump
(seconds)
DHW requested rate RPM or %
DHW sensor state
None, Normal, Open, Shorted,
Outside high range, Outside low
range, Not reliable (None = no outlet
sensor)
DHW OFF setpoint
Setpoint plus hysteresis
DHW setpoint
Temp setting between -40 °F to 266 °F
(-40 °C to 130 °C)
DHW ON setpoint
Setpoint minus hysteresis
DHW setpoint source Normal, TOD, Outdoor reset
DHW status
Disabled, Normal, Suspended
DHW temperature
DHW temperature (same as bar
graph)
Table 45. DHW Hydronic Status. (Continued)
Data Comment