DETAILS
Details of the hydronic or steam system is accomplished
through the detail status pages. The detail status page is
shown below.
Screens will appear only if they are configured for your
system.
Information shown is current status. For example: firing rate is
the current fan speed or motor position; timing shown is
current time Sola is at.
Fig. 61. Hydronic CH detail status page.
Status information on the detail status page is organized into
groups and displayed on the page one group at a time. The
user moves from one group to another using the left and right
arrow buttons.
Status data on the detail status page is displayed in a menu
for the group that is currently displayed. If more status items
exist in the group than will fit on the screen, a vertical scroll
bar allows the user to see all status data. If the user selects a
line of status data in the menu, it will expand in bigger, more
easily readable text, as show in Fig. 62. Additional information
about Status data and groups that are displayed are provided
in the R7910 or R7911 Status section of this document.
Fig. 62. Hydronic “expanded” detail status.
R7910 or R7911 Status
Data in Tables 44–Table 55 are displayed on the R7910
Hydronic or R7911 Steam status pages. A complete list of
Status tables can be found in Table 59 on page 42.
The CH status data shown in Table 44 displays first when the
CH Hydronic heating loop is selected on the Home page.
Fig. 63. CH Hydronic Status menu (top).
Table 44. CH Hydronic Status.
Data Comment
CH enable
Enabled, Disabled
CH burner demand
On or Off
CH pump
On or Off
CH pump demand
On or Off
CH pump overrun
time
Running overtime for CH pump
(seconds)
CH requested rate
RPM or %
CH OFF setpoint
Setpoint plus hysteresis
CH setpoint
Temp setting between -40 °F to 266 °F
(-40 °C to 130 °C)
CH ON setpoint
Setpoint minus hysteresis
CH setpoint source
Normal, TOD, Outdoor reset, Remote
control
CH status
Disabled, Normal, Suspended
Demand source
Sensor only, Sensor and Stat terminal,
Sensor and Remote Stat, LCI and
sensor
Outlet high limit
Yes or No
Outlet high limit
setpoint
Temp setting between -40 °F to 266 °F
(-40 °C to 130 °C)
Outlet sensor state
None, Normal, Open, Shorted,
Outside high range, Outside low
range, Not reliable (None = no outlet
sensor)
Outlet temperature
Outlet temperature (same as bar
graph)