23
65-0315—02
Annunciation Configuration
Parameters
Table 25 displays annunciation configuration parameters.
Fig. 43. Annunciation configuration example.
Safety Configuration Parameters
Table 26 through 29 display safety parameters.
NOTE: Login is required to change Safety Parameters
and the SOLA Control will go to a Lockout 2
“waiting for safety data verification” when a
change is made.
Fig. 44. Burner Control Interlocks control.
Table 25. Annunciation Configuration Parameters.
Parameter Comment
Annunciation enable Enabled
Disabled
Annunciator (1–8)
location
01 - Annunciator 1
02 - Annunciator 2
03 - Annunciator 3
04 - Annunciator 4
05 - Annunciator 5
06 - Annunciator 6
07 - Annunciator 7
08 - Annunciator 8
PII - Pre-Ignition ILK
LCI - Load Control Input
ILK - Interlock
Annunciator (1–8)
short name
Up to 3 characters
Annunciator (1–8)
name
Up to 20 characters
Table 26. Burner Control
Interlocks Configuration.
Parameter Comment
PII enable
Enabled
Disabled
LCI enable
Enabled
Disabled
Interrupted air switch
(IAS) enable
Enable during purge and ignition
Disabled
Enable during purge
Interlock (ILK) start
check enable
No ILK check
ILK check
ILK/IAS open
response
Recycle
Lockout
ILK bounce detection
enable
Enabled
Disabled
Purge rate proving
Fan Speed
High Fire Switch
None
Lightoff rate proving
Fan Speed
Low Fire Switch
None