65-0315—02
22
Anti-Condensation Configuration
Parameters (R7910 Hydronic Control
Only)
Table 23 displays anti-condensation parameters. Use the left
and right arrows to switch between Central Heat, Domestic
Hot Water, Frost Protection, and Priority parameters.
Fig. 41. Anti-condensation configuration.
Frost Protection Parameters
(R7910 Hydronic Control Only)
Table 24 displays frost protection parameters.
Fig. 42. Frost Protection configuration.
Table 23. Anti-Condensation Configuration Parameters.
Parameter
Comment
CH Enable
Enabled
Disabled
CH Setpoint
32 °F to 250 °F (0 °C to 121 °C)
DHW Enable
Enabled
Disabled
DHW Setpoint
32 °F to 250 °F (0 °C to 121 °C)
Frost Protection
Enable
Enabled
Disabled
Anticondensation
Priority
Anticondensation is more important
than (check those that apply):
Stack limit
Delta T limit
Slow start
Forced rate
Outlet high limit
Table 24. Frost Protection Configuration Parameters.
Parameter Comment
CH frost protection
enable
Enabled
Disabled
DHW frost protection
enable
Enabled
Disabled
Lead Lag frost
protection enable
Enabled
Disabled
Outdoor frost
protection setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
(applicable for CH only)
Lead Lag frost
protection rate
___%
CH pump frost
overrun time
___hour ___min ___sec
DHW pump frost
overrun time
___hour ___min ___sec