Fire Alarm Control Panel IQ8Control C / M
74
FB 798951.10.GB0 / 04.15
S1
Rotary address switch to select panel address factor x1
S2
Rotary address switch to select panel address factor x10
X1
64 pin connector for the micro module slot inside the FACP
X4 / X5
jumpers for configuration of the terminals IN/OUT (terminal 1+2 and 3+4)
X4
X4
1 2
3 4
5
6
7 8
copper cable
connected
fibre optics converter
terminal card
1 2
3 4 5
6
7 8
X5
X5
fibre optic cable
connected
fibre optics converter
terminal card
If data is transferred via fibre optic, two fibre optic fibre converters are always required for a data path
between the devices.
The documentation 798636 and 798963.10 contains more information about fibre optic converters.
LED
Status and error indication
red
on
- communication error between essernet
®
micro module and FACP
green
flashing
- communication with other network devices
yellow
on
- communication error (A/B mode)
unidirectional communication
All other LED display combinations mean that there is a fault in the essernet
®
module or that
measuring operation is active.
Connect cable shielding to the appropriate terminals !
The data signalling rate and connection cable to be used is governed by the module type
installed. In a network you may only use essernet
®
modules with the same data signalling rate.