Fire Alarm Control Panel IQ8Control C / M
56
FB 798951.10.GB0 / 04.15
6.4.1 Connecting fire department operating panel
X4
bottom - terminals
top - terminals
Wiring differs from area to area and is
governed by the requirements of the
regional fire department.
A 12 V DC voltage is required for
operation.
IN
1
IN
8
IN
2
IN
3
IN
4
IN
5
IN
6
IN
7
X4
FD call LED on
(IN1 on GND)
(closer)
MB disconnected
acoustic signals off
check MB
reset FACP
fire control off / revision
do not use
top
terminals
do not use
If the terminal IN8 (fire control off / revision) is not used, jumper BR21 must always be fitted at
position 2-3 !
Current load per output (OUT1 to OUT 8) max. 25 mA.
Observe permitted torque (max. 0.4 Nm) of the terminals!
OU
T1
OU
T8
OU
T2
OU
T3
OU
T4
OU
T5
OU
T6
OU
T7
X4
MB activated
extinguishing system activated
common fire
MB disconnected
MB activation prevent
do not use
acoustic signals off
fire control off (revision)
bottom
terminals
Fig. 47: Connection terminals fire department operating panel