Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15
65
IQ8Control C
The Field device module with a single micro module slot (Part No. 772478) must be placed on the >System
connector 1< of the Basic module. This connector is normally used by the Field device module. Without the field
device module a system configuration in accordance to the standards is not possible (refer to Chapter 4).
IQ8Control M
Up to two connectors are available for Extension modules (Field device and or Extension module). Normally the
lower >connector 2< is used to connect an Extension module. If required the upper >connector 1< may be used
too for an Extension module. In this case the integration of an Field device module is impossible. In this case
mounting of the field device is not possible anymore (see Chapter 4).
Extension module with a single micro module slot (Part No. 772478)
This Extension module must be configured in the panels data programming as a Field device module.
X 1a/2b/3c
connector
>System connector 1 or 2< of the Basic modules
Refer to note!
X11a/12b
Connector for a micro module
(Do not connect an essernet
®
micro module) Refer to note!
Refer to note!
X 10
Terminals for the micro module wiring.
Extension module with three micro module slots (Part No.772476)
Only FACP IQ8Control M configurable.
LED V1
ON – Common fire alarm
LED V2
ON – CPU failure
place 1
Micro module slot only for micro module
Do not connect an
essernet
®
micro module.
Refer to note!
place 2
Micro module slot only for micro module
place 3
Micro module slot only for micro module
X22
terminal for micro module slot 1
X23
terminal for micro module slot 2
X24
terminal for micro module slot 3
X 4/5/6
Plug contact of
>System connector 1 or 2< of the Basic module
Refer to note!
If an essernet
®
micro module is installed, this module can only be operated on the micro module
slot of the Basic module.
6.5.1 Technical Data Extension module
Operating voltage
: Internal via the power supply module, +5 V DC
Quiescent current
: approx. 10 mA
Compatibility :
Part
No.772478
Extension module with one micro module slot
Part No.772476
Extension module with three micro module slots