Fire Alarm Control Panel IQ8Control C / M
132
FB 798951.10.GB0 / 04.15
20 Power supply for the built-in printer
The internal power supply of the built-in printer is provided by the basic module terminals of the FACP.
switched
+12 V UBext.
+UBext.
BR7
Printer
Pr
in
te
r
GND
F4
+UBext T2A
GND
+UBext.
+12 V DC
ext. power supply
+UBext.
BR7
Printer
Pr
in
te
r
GND
F4
+UBext T2A
+UBext.
Fig. 111: Internal Power supply for the built-in printer
Fig. 112: External Power supply for the built-in printer
To use an external 12 V DC power supply unit (e.g. Part-No. 805683) open solder jumper
BR7
!
Observe permitted torque (max. 0.4 Nm) of the terminals!
Accessories for the built-in printer
Paper for Printer
(Part No. 736235)
(Part No. 736233 / -34)
Dimensions: W = 58 mm, L = 25 m