Fire Alarm Control Panel IQ8Control C / M
116
FB 798951.10.GB0 / 04.15
Trouble
Code No.
Possible cause
1st. measure
2nd. measure
012
1)
Detector is soiled or damp.
Clean detector and check it with
programming software tools
8000.
Check the installed detector if
the surrounding area is
humid. Use protective
measures if necessary, e.g.
series 9x00 detectors: surface
mount adapter 781495 or
781497/98 uses base
adapter.
2)
CO sensor is faulty.
Replace detector.
Return faulty detectors to the
manufacturer.
013
1)
Air speed too high at site
of installation.
2)
Detector is soiled with
conductive substance and
may be installed in damp
environment.
Clean detector and check it with
programming software tools
8000.
Using another detector type.
3)
CO sensor has temporarily
left its working range (e.g.
due to oversaturation).
Reset detector and recheck.
If the error occurs again,
return detector to
manufacturer for checking.
014
Short-circuit at the
temperature sensor.
Replace detector and return to
manufacture.
---
015
1)
Faulty bonding of the
temperature sensor.
2)
First installation at a cool
place.
Adjust detector to ambient
temperature with programming
software tools 8000.
Replace detector and return
to manufacture.
016 see
001
---
---
017
1)
Detector is soiled with a
conductive substance or
installed in damp
surroundings.
2)
Faulty detector.
Clean detector and check it with
programming software tools
8000.
Replace detector and return
to manufacture.
3)
CO sensor is faulty. It is
possible that the rel.
humidity is always at a
very low value in the area
surrounding the detector.
Replace detector.
Return faulty detectors to the
manufacturer.
018
1)
Detector is soiled with a
conductive substance or
installed in damp
surroundings.
2)
Faulty detector.
Clean detector and check it with
programming software tools
8000.
Replace detector and return
to manufacture.
019
1) Detector is soiled with oily
substance.
Clean detector and check it with
programming software tools
8000.
---
2) CO sensor is faulty.
Replace detector.
Return faulty detectors to the
manufacturer.
020
021
Current levels not correct on
loop.
Check numbers of detectors,
loop resistor and loop length.
Check detector base wiring.
022
Detector unable to correctly
activate its base circuit board.
Check detector base wiring.
---