Fire Alarm Control Panel IQ8Control C / M
62
FB 798951.10.GB0 / 04.15
CPU failure mode function of relays K2, K3 and K4
1
2
3
BR 5 BR 4 BR 3
K3
K4
K2
Fig. 54: Location of the emergency mode jumpers BR3 to 5 on the Field device module
K2
K3
K4
BR
4
1
2
3
BR
3
1
2
3
BR
5
1
2
3
Jumper X in position 1/2
No activation of the relay while the Fire Alarm Control
Panel is in CPU failure mode (state on leaving factory).
BR
4
1
2
3
BR
3
1
2
3
BR
5
1
2
3
Jumper X in position 2/3
Relay also activated while the Fire Alarm Control Panel is
in CPU failure mode.
Used if a common function is programmed for the relays,
such as >common fire<, >common alarm< and >common
disconnection<.