Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15
105
10.7 Printer function
Under this menu point, the protocol printer connected to the Fire Alarm Control Panel (internal printer and/or
external serial printer) can be switched on or off. In addition, the contents of the internal event memory of the
control panel can be printed out on a local protocol printer.
The activation of other control panel printers in the essernet
®
is impossible.
Internal protocol printer
The internal protocol printer is selected with a (max.) four-digit number. This number consists of the control panel
number (e.g. 1 to 31 in an essernet
®
) and the number "01".
Example: panel number 01
Nr. of the internal protocol printer 01
10
panel number 05
Nr. of the internal protocol printer 05
10
External protocol printer
The external protocol printer is selected by the primary loop number of the RS 232/TTY module to which the
printer is connected. The primary loop number consists of the number of the FACP, the micro module board and
the slot in which the RS232 / TTY-Module is fitted.
Switching off the protocol printer
By the first activation of the menu options >Printer function<, the printer number is automatically allocated to the
internal protocol printer if installed. This allocation can be removed by pressing the >Zone< key.
Func.menu
Repeat
Select
Switch off
Switch on
Print event mem
Printer
:
Printer
Fig. 94: Function menu
Enter the number of the printer which is to be switched off (primary loop number of the serial interface) and
press the >Select< function key
Enter the number of the desired function (1 = Switching off) or select the menu options Switching off with the
cursor keys and press the >Function< key