5. Configuration and Function of Internal Memory
5.3. Operation parameters settings area
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
79
September 2010
Honeywell
Address 2 - Output data format
The range of digital output data for analog input is specified for each channel.
1.
If the output data range is not specified, the range of all the channels is set to 0 ~
16000.
2.
Setting range of digital output data range is as explained below.
Precise value has the following digital output ranges for the analog input range.
2MLF-AV8A
Analog input
Digital output
-10 ~ 10V
0 ~ 10V
0 ~ 5V
1 ~ 5V
Precise Value
-10000 ~ 10000
0 ~ 10000
0 ~ 5000
1000 ~
5000
2MLF-AC8A
Analog input
Digital output
4 ~ 20mA
0 ~ 20mA
Precise Value
4000 ~ 20000
0 ~ 20000