5. Configuration and Function of Internal Memory
5.3. Operation parameters settings area
82
Analog Input Module 2MLF-AV8A, AC8A User's Guide
R200
Honeywell
September 2010
Address 13 - Average process method (address number 13)
This area is used for specifying average processing method. The available options are
count average and time average. If neither is specified, all the channels are set to count
average process by default.
ATTENTION
This setting is effective only when the average process is set to ‘Enable’.
Address 14-21 - Average value
Setting range of time/count average’s constant value is explained as follows:
•
Setting range of time average: 4 ~ 16000 (ms)
•
Setting range of count average: 2 ~ 64000 (times)
If it exceeds the range:
1.
Error No. 60X is generated if time average range is exceeded.
2.
Error No. 70X is generated if count average range is exceeded.
The above error codes are available on address 22. If the above error occurs, the default
values are applied for average processing.
Default values are time average: 4, Frequency average: 2
The process value of time/count average is as stored below:
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...