5. Configuration and Function of Internal Memory
5.5. PUT/GET function block use area (parameter area)
98
Analog Input Module 2MLF-AV8A, AC8A User's Guide
R200
Honeywell
September 2010
Precise value has the following digital output range for analog input range.
−
2MLF-AV8A
Analog input
Digital output
-10 ~ 10V
0 ~ 10V
0 ~ 5V
-1 ~ 5V
Precise value
-10000 ~
10000
0 ~
10000
0 ~ 5000 1000 ~ 5000
−
2MLF-AC8A
Analog input
Digital output
4 ~ 20mA
0 ~
20mA
Precise value
4000 ~
20000
0 ~
20000
Filter process setting
1.
You can enable/disable filter process per channel.
2.
If filter process is not set; all channels are set as enable.
3.
The following figure is an example for using filter CH4.