R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
15
September 2010
Honeywell
1. Introduction
1.1 Overview
This user’s guide describes two analog input modules.
•
2MLF-AV8A type voltage to digital conversion module
•
2MLF-AC8A type current to digital conversion module.
Both A/D conversion modules are used for converting analog signals (voltage or current
input) from PLC’s external device to signed 16-bit binary data of digital value. They are
used with MasterLogic-200 CPU module, ML200-IEC (2MLI-CPUU), and ML200R
(2MLR-CPUH).
1.2 Features
1.
Module selection: You can choose the module depending on input signal type.
a)
2MLF-AV8A: 8 channels, voltage input
b)
2MLF-AC8A: 8 channels, current input
2.
High speed A/D conversion @ 250 µs/channel.
3.
High conversion accuracy of ±0.2% (ambient temperature of 25 ± 5
o
4.
High resolution (16-bit) of digital value, that is, 1/16000.
C).
5.
Simplified module setup/monitoring through GUI:
Setting up an A/D conversion module’s operation parameters (that is, range, filter,
and so on.) was traditionally a cumbersome process using repetitive sequences of
ladder programs. This is now achieved using a user-friendly graphical user interface
(GUI) in SoftMaster I/O Parameters. In addition, the A/D conversion value can also
be easily monitored using the Special Module Monitoring function.
6.
Multiple digital output data formats: Fours formats are available, as specified
below:
a)
Unsigned value: 0 ~ + 16000
b)
Signed value: - 8000 ~ + 8000
c)
Precise value: Refer to Performance specifications.
d)
Percentile value: 0 ~ + 10000
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...