2. Specifications
2.1. Performance specifications
22
Analog Input Module 2MLF-AV8A, AC8A User's Guide
R200
Honeywell
September 2010
Item
Specifications
2MLF-AV8A (Voltage Input Type)
2MLF-AC8A (Current Input Type)
Signed value
-8000 ~ 8000
Precise value
4000 ~ 20000
0 ~ 20000
Percentile value
0 ~ 10000
•
16-bit binary value (data: 14 bits)
•
You can individually set the format of digital output data for each channel either from
user program or through user-friendly GUI I/O parameter function in SoftMaster.
Maximum
resolution
Analog input range
Resolution
(1/16000)
Analog input
range
Resolution
(1/16000)
1 ~ 5V
0.250mV
4 ~ 20mA
1.0µA
0 ~ 5V
0.3125mV
0 ~ 10V
0.625mV
0 ~ 20mA
1.25µA
-10 ~ 10V
1.250mV
Accuracy
±0.2% or less (when ambient temperature is 25 ±5
o
C)
±0.3% or less (when ambient temperature is 0 ~ 55
o
C)
Maximum
conversion speed
250μs/channel
Absolute maximum
input
±15V
±30mA
Analog input
channels
8 channels/ module
Isolation method
Photo-coupler isolation between input terminal and PLC power (no isolation between
channels)
Terminal
connected
18-point terminal
I/O addresses
assigned
Fixed type: 64 points, Variable type: 16 points
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...