2. Specifications
2.3. Characteristics of I/O conversion
32
Analog Input Module 2MLF-AV8A, AC8A User's Guide
R200
Honeywell
September 2010
Digital output value for voltage input characteristics is as specified below:
(Resolution (based on 1/16000): 0.625mV)
Digital output
range
Analog input voltage (V)
-0.12
0
2.5
5
7.5
10
10.11
Unsigned value
(-192 ~ 16191)
-192
0
4000
8000
12000
16000
16191
Signed value
(-8192 ~ 8191)
-8192
-8000
-4000
0
4000
8000
8191
Precise value
(-60 ~ 5059)
-120
0
2500
5000
7500
10000
10119
Percentile value
(-120 ~ 10119)
-120
0
2500
5000
7500
10000
10119
4.
If the range is DC-10 ~ 10V
On
I/O Parameters Setting
window, set
Input
Range
to -10 ~ 10V.
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...