5. Configuration and Function of Internal Memory
5.5. PUT/GET function block use area (parameter area)
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
101
September 2010
Honeywell
Average process setting
1.
You can enable/disable average process per channel.
2.
When disabling the average process, all channels are set as sampling process.
3.
The following figure is an example for setting average process for channel 7.
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
-
-
-
-
-
-
-
-
CH7
CH6
CH5
CH4
CH3
CH2
CH1
CH0
BIT
Description
0
Disable
1
Enable
Average process method setting
1.
In average process method, there are Count average, and Time average.
2.
All channels execute average process by Count if Time/Count average process is
not set.