2. Specifications
2.3. Characteristics of I/O conversion
38
Analog Input Module 2MLF-AV8A, AC8A User's Guide
R200
Honeywell
September 2010
Accuracy
Accuracy of digital output value does not change even if you change the input range.
Figure 8 shows the change range of the accuracy at ambient temperature of 25 ± 5
o
C
with analog input range as -10 ~ 10V and digital output type as unsigned value. ±0.2% at
ambient temperature of 25 ± 5
o
C, and ±0.3% at ambient temperature of 0 ~ 55
o
C.
0
-10 V
0 V
8000
10 V
16000
Analog Input Voltage
D
ig
ita
l O
ut
pu
t V
al
ue
15968
16032
-32
32
Figure 8 – Accuracy