7. Troubleshooting
7.1 Error codes
Errors which occur when A/D conversion module’s RUN LED blinks are as described in
Table 7 – List of error codes
Error Code
(Dec)
Description
RUN LED
status
10
Module error (ASIC Reset Error).
Flickers every
0.2s.
11
Module error (ASIC RAM or Register Error).
20
Module error (A/D Conversion Error).
30
Module error (EEPROM Error).
40#
Module error (Offset value with the range of 1 ~ 5V or 4 ~ 20mA is
set greater than or equal to Gain value.)
Flickers every
1s.
41#
Module error (Offset value with the range of 0 ~ 5V or 0 ~ 20mA is
set greater than or equal to Gain value.)
42#
Module error (Offset value with the range of 0 ~ 10V is set greater
than or equal to Gain value.)
43#
Module error (Offset value with the range of -10 ~ 10V is set greater
than or equal to Gain value.)
50#
Filter constant setting range exceeded.
60#
Time average setting range exceeded.
70#
Count average setting range exceeded.
80#
Analog input range setting error (only for 2MLF-AC8A).
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...