R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
69
September 2010
Honeywell
5. Configuration and Function of Internal Memory
5.1 Internal memory configuration
A/D conversion module has its own internal memory to transmit/receive data to/from
PLC CPU.
The following table lists the details of the I/O area of A/D converted data..
Table 5 – I/O area of A/D converted data
Address
Assigned
Global Variable
Details
R/W Directio
n
%UXa.b.0
%UXa.b.15
_ab_ERR
_ab_RDY
Module ERROR
Module READY
R
A/D
→
CPU
%UXa.b.16
%UXa.b.17
%UXa.b.18
%UXa.b.19
%UXa.b.20
%UXa.b.21
%UXa.b.22
%UXa.b.23
_ab_CH0_ACT
_ab_CH1_ACT
_ab_CH2_ACT
_ab_CH3_ACT
_ab_CH4_ACT
_ab_CH5_ACT
_ab_CH6_ACT
_ab_CH7_ACT
CH0 Active
CH1 Active
CH2 Active
CH3 Active
CH4 Active
CH5 Active
CH6 Active
CH7 Active
R
A/D
→
CPU
%UWa.b.2
_ab_CH0_DATA
CH0 Output
R
A/D
→
CPU
%UWa.b.3
_ab_CH1_DATA
CH1 Output
%UWa.b.4
_ab_CH2_DATA
CH2 Output
%UWa.b.5
_ab_CH3_DATA
CH3 Output
%UWa.b.6
_ab_CH4_DATA
CH4 Output
%UWa.b.7
_ab_CH5_DATA
CH5 Output
%UWa.b.8
_ab_CH6_DATA
CH6 Output
%UWa.b.9
_ab_CH7_DATA
CH7 Output
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...