background image

Quick Response
Extended Coverage
Horizontal Sidewall Sprinklers
SuperNova™ S126
K=8.0, 3/4" NPT

GENERAL DESCRIPTION

The Star SuperNova S126, 8.0 K-Factor, QR-EC Horizon-
tal Sidewall Sprinklers are quick response - extended cov-
erage, fusible solder type spray sprinklers designed for
use in hydraulically calculated sprinkler systems in light
hazard, commercial occupancies such as churches, res-
taurant seating areas, hotels, educational facilities, of-
fices, etc. With coverage areas up to 16 feet (4.9 m) wide
by 24 feet (7.3 m) long, they are designed for installation
along a wall or the side of a beam and just beneath a
smooth and level ceiling. Horizontal sidewall sprinklers
are commonly used instead of pendent or upright sprin-
klers because of aesthetics or building construction con-
siderations, where piping across the ceiling is not desir-
able.

WARNINGS

The SuperNova S126 Sprinklers described herein must
be installed and maintained in compliance with this docu-
ment, as well as with the applicable standards of the Na-
tional Fire Protection Association, in addition to the stand-
ards of any other authorities having jurisdiction. Failure to
do so may impair the integrity of these devices.

The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.

OPERATION

The fusible link (heat collector) assembly is comprised of
two link halves which are joined together by a thin layer
of solder. When the rated temperature is reached, the sol-
der melts and the two link halves separate, which then al-
lows the sprinkler to activate and flow water.

TECHNICAL DATA

Approvals

UL and ULC Listed. FM Approved.
NYC Accepted (MEA 188-99-E).
(The approvals apply only to the service conditions
indicated in the Design Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

3/4 inch NPT

Discharge Coefficient

K = 8.0 GPM/psi

1/2

(115,2 LPM/bar

1/2

)

Temperature Rating

140°F/60°C or 165°F/74°C

Finish

Sprinkler: Natural Brass or Chrome Plated

Physical Characteristics (Ref. Figure 1)

The SuperNova S126 utilizes a bronze frame. The strut
and hook are bronze; the button and deflector are brass;
the orifice seal is Teflon

†

; and, the two halves of the fus-

ible link assembly are nickel.

Patents
U.S.A. Patent No. 4,901,799 applies to the SuperNova
S126 QR-EC Horizontal Sidewall Sprinklers.

DESIGN CRITERIA

The 8.0 K-Factor, SuperNova S126 (SIN S1868) QR-EC
Horizontal Sidewall Sprinklers must only be installed and
utilized for the protection of Light Hazard Occupancies un-
der smooth and level ceilings, as well as in accordance
with the criteria given in Table A or B, as applicable. Instal-
lation of SuperNova S126 Sprinklers in recessed escutch-
eons will void the sprinkler’s Approvals and/or Listings.

SIN S1868

QR-EC Horizontal Sidewall

†

DuPon

t

Regi

ste

red

Trad

emar

k

Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500

3-01

1-2.3.21

TYCO FIRE PRODUCTS

OBSOLETE

Содержание Star SuperNova S126

Страница 1: ...at collector assembly is comprised of two link halves which are joined together by a thin layer of solder When the rated temperature is reached the sol der melts and the two link halves separate which then al lows the sprinkler to activate and flow water TECHNICAL DATA Approvals UL and ULC Listed FM Approved NYC Accepted MEA 188 99 E The approvals apply only to the service conditions indicated in ...

Страница 2: ... 5 5 16 x 18 4 9 x 5 5 13 1 0 90 29 110 NOTES a For use in QR EC and EC Light Hazard Occupancy automatic sprinkler system applications per NFPA 13 b For use in EC Light Hazard Occupancy automatic sprinkler system applications per NFPA 13 c Requirement is based on minimum flow in GPM from each sprinkler The indicated residual pressures are based on the nominal K factor d The centerline of the sprin...

Страница 3: ...mitted ceiling slope for S126 Sprinklers is a 1 inch 25 4 mm rise over a 12 inch 304 8 mm horizontal run with ceiling sloping downwards from the wall on which the sprinkler is located f The deflector boss to wall distance of 2 to 2 3 4 inches 50 to 70 mm provides a heat responsive element to wall distance of 3 4 to 1 1 2 inches 20 to 40 mm Application QR EC a Coverage Area W x L FT x FT m x m Mini...

Страница 4: ...use and service This warranty will expire ten 10 years from date of shipment by Tyco Fire Products No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Prod ucts or for products and components which have been subject to misuse improper installation corrosion or which have not been installed maintained modified or re paired in accordan...

Отзывы: