7. Troubleshooting
7.2. Troubleshooting
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
131
September 2010
Honeywell
7.2 Troubleshooting
RUN LED blinks
Error Code
(Dec)
Error Details
Action
40#
Module Offset/Gain error
Turn the power ON/OFF. If the error recurs, it is
likely that the module is defective. Contact the
nearest Honeywell agency or branch office.
41#
42#
43#
50#
Filter constant setting
range exceeded
Change filter constant setting value within 1 ~ 99.
60#
Time average setting
range exceeded
Change time average setting value within 4 ~
16000.
70#
Frequency average
setting range exceeded
Change frequency average setting value within 2
~ 64000.
80#
Analog input range error
(Only 2MLF-AC8A)
Refer to Address 1- input Voltage/Current section
and then change the analog input range.
RUN LED blinks
RUN LED blinks every 0.2 sec.
Switch the module power OFF and then turn it ON. If the
error recurs, it is likely that the module defective. Contact the
nearest Honeywell office or authorized service engineer.
RUN LED blinks every 1 sec.
Run parameters setting error. Check the error code in the
table below.
Yes
No
Yes
Содержание 2MLF-AC8A
Страница 14: ...Contents Figures xiv Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 106: ......
Страница 114: ...6 Programming 6 3 Basic program 114 Analog Input Module 2MLF AV8A AC8A User s Guide R200 Honeywell September 2010 ...
Страница 117: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 117 September 2010 Honeywell ...
Страница 119: ...6 Programming 6 3 Basic program R200 Analog Input Module 2MLF AV8A AC8A User s Guide 119 September 2010 Honeywell ...
Страница 140: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...