2. Specifications
2.3. Characteristics of I/O conversion
30
Analog Input Module 2MLF-AV8A, AC8A User's Guide
R200
Honeywell
September 2010
Digital output value for voltage input characteristics is as specified below.
(Resolution (based on 1/16000): 0.3125mV)
Digital output
range
Analog input voltage (V)
-0.06
0
1.25
2.5
3.75
5
5.05
Unsigned value
(-192 ~ 16191)
-192
0
4000
8000
1200
0
16000
16191
Signed value
(-8192 ~ 8191)
-8192
-
8000
-4000
0
4000
8000
8191
Precise value
(-60 ~ 5060)
-60
0
1250
2500
3750
5000
5060
Percentile value
(-120 ~ 10119)
-120
0
2500
5000
7500
10000
10119
3.
If the range is DC 0 ~ 10V