2. Specifications
2.3. Characteristics of I/O conversion
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
29
September 2010
Honeywell
Digital output value for voltage input characteristics is as specified below.
(Resolution (based on 1/16000): 0.25mV)
Digital output range
Analog input voltage (V)
0.952
1
2
3
4
5
5.047
Unsigned value
(-192 ~ 16191)
-192
0
4000
8000
12000 16000
16191
Signed value
(-8192 ~ 8191)
-8192
-8000
-4000
0
4000
8000
8191
Precise value
(952 ~ 5048)
952
1000
2000
3000
4000
5000
5048
Percentile value
(-120 ~ 10119)
-120
0
2500
5000
7500
10000
10119
2.
If the range is DC 0 ~ 5V
On the
I/O Parameters Setting
window, set
Input Range
to 0 ~ 5V.