GR4000 Installation Guide Version 1.00 - Preliminary
68
520-10-014-20X
(4) Dual power supply system
With the redundancy of a power supply unit, you can have a dual power supply system
by providing the electricity to each power supply unit from different power sources.
2.4.2 Equipment for DC Power Supply Unit
(1) DC-48V/ DC-60V Power Cable
All power connection wiring should conform to the rules and regulations in the National
Electrical Code (NEC) as well as any local codes.
The diameter of a DC cable to be used differs depending on the type of a power supply
unit.
Use the following rated cables for POW-HSDCE(DC80001-U) and POW-
MSDCE(DC160001-U). (For the detail specifications of the cables to be used for each
GR4000 model, see Table 2.4-5.)
1) POW-HSDCE(DC80001-U)
:
AWG8
2) POW-MSDCE(DC160001-U)
:
AWG6
The DC power cords should terminate with the cable terminals on the side of power
supply shelves.
The cable terminals used for POW-HSDCE(DC80001-U) and POW-MSDCE(DC160001-
U) are allowed to have only one hole and should meet the following specifications.
1) POW-HSDCE(DC80001-U)
:
M5 terminal
,
rated -48VDC/21A or -60VDC/17A, UL
product. For its shape, see Figure 2.4-2.
2) POW-MSDCE(DC160001-U)
:
M6 terminal
,
rated -48VDC/42A or -60VDC/34A, UL
product. For its shape, see Figure 2.4-2.
Consider the distance from a cable clamper to a terminal board when preparing the DC
power cable. The form of a terminal board on the power supply unit is shown in Figure
2.4-3.
Table 2.4-5 Specifications of DC power cables
Cable spec.
Model
Number of core wires
AWG No.
Outer diameter of cables
GR4000
-
80E2
8
φ
23mm or less
GR4000
-
160E2
GR4000
-
320E
3 core wires twisted together
6
φ
27mm or less
Figure 2.4-2
Dimensions of DC power terminals
WARNING: WHEN USING A DC POWER CABLE, ATTACH AN INSULATING SHEATH AT
THE CABLE TERMINAL. USING AN UNSHEATHED DC POWER CABLE COULD
CAUSES AN ELECTRIC SHOCK.
DC cable terminal for GR4000-80E2
φ
5.2
~
5.6
12.4 Max.
15 Min.
φ
6.3
~
6.9
12.4 Max.
15 Min.
Unit
:
mm
DC cable terminal for GR4000-160E2/GR4000-320E
Insulating sheath
Insulating sheath
Содержание GR4000 Series
Страница 1: ...Hitachi Gigabit Router GR4000 Series Installation Guide Version 1 00 Preliminary ...
Страница 98: ...GR4000 Installation Guide Version 1 00 Preliminary 80 520 10 014 20X This page left intentionally blank ...
Страница 152: ...GR4000 Installation Guide Version 1 00 Preliminary 134 520 10 014 20X ...
Страница 164: ...GR4000 Installation Guide Version 1 00 Preliminary 146 520 10 014 20X This page left intentionally blank ...