13.2 Input Specifications/Output Specifications/Measurement Specifications
210
(27) Harmonic voltage and harmonic current (including fundamental component) (Uharm/Iharm)
Measurement method
Compliant with IEC61000-4-7:2009
Indicated harmonic voltage and harmonic current values incorporate inter-harmonics components
adjacent to the next whole-number harmonic component after harmonic analysis. (For details see
"13.8 Calculation Formula" (p.232).)
Measurement accuracy is specified for input that is 10% to 200% of IEC61000-2-4 Class 3.
Analysis window width
10 cycles (50 Hz), 12 cycles (60 Hz), or 80 cycles (400 Hz)
Number of window points
Rectangular, 4096 points
Displayed item
From the 0th to 50 th order (with a fundamental wave of 40 Hz to 70 Hz)
From the 0th to 10 th order (with a fundamental wave of 360 Hz to 440 Hz)
Select either RMS or content percentage (When using content percentage, Zero-display range
causes all orders to be given as 0% when the RMS value is 0.)
Measurement range
Harmonic voltage: 600.00 V
Harmonic current: Varies with the current sensor used (see input specifications).
Measurement accuracy
See measurement accuracy with a fundamental wave of 50 Hz/60 Hz and measurement accuracy
with a fundamental wave of 400 Hz.
Event threshold
Level
Harmonic voltage: 0.00 to 780.00 V (order 0: specified as absolute value)
Harmonic current : From 0 to (1.3 × current range) (see input specifications) (order 0: specified
as absolute value).
Content percentage
0.00% to 100.00%
Event IN
Start of approx. 200 ms aggregation in which readings were greater than the threshold for each order
Event OUT
Start of approx. 200 ms aggregation in which readings were less than (threshold - hysteresis) for each order
Multiple-phase system treatment
Separate by channel
Saved waveforms
Event waveforms
Constraints
When using an AC-only current sensor, the 0th order is not specified for current and power.
(28) Harmonic power (including fundamental component) (Pharm)
Measurement method
Compliant with IEC61000-4-7:2009
Indicates harmonic power values consisting of harmonic power for each channel and the sum of
multiple channels. (For details see "13.8 Calculation Formula" (p.232).)
Analysis window width
10 cycles (50 Hz), 12 cycles (60 Hz), or 80 cycles (400 Hz)
Number of window points
Rectangular, 4096 points
Displayed item
From the 0th to 50 th order (with a fundamental wave of 40 Hz to 70 Hz)
From the 0th to 10 th order (with a fundamental wave of 360 Hz to 440 Hz)
Select either RMS or content percentage (When using content percentage, Zero-display range
causes all orders to be given as 0% when the RMS value is 0.)
Measurement range
See power ranges.
Measurement accuracy
See measurement accuracy with a fundamental wave of 50 Hz/60 Hz and measurement accuracy
with a fundamental wave of 400 Hz.
Event threshold
Harmonic power: From 0 to (1.3 × current range) (specified as absolute value)
Event IN
Start of approx. 200 ms aggregation in which the reading is greater than the threshold (when the
threshold is positive) or less than the threshold (when the threshold is negative)
Event OUT
Start of the approx. 200 ms aggregation in which the reading is less than (threshold - hysteresis)
(when the threshold is positive) or greater than (thr hysteresis) (when the threshold is neg-
ative) in the EVENT IN state
Multiple-phase system treatment
Separate by channel
Saved waveforms
Event waveforms
Constraints
When using an AC-only current sensor, the 0th order is not specified for current and power.
HIOKI PQ3198A961-03
Содержание PQ3198
Страница 2: ...HIOKI PQ3198A961 03...
Страница 6: ...Contents iv HIOKI PQ3198A961 03...
Страница 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Страница 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Страница 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Страница 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Страница 116: ...6 4 Displaying Harmonics 110 Holding the display Hold Measured values and waveforms will be held HIOKI PQ3198A961 03...
Страница 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Страница 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Страница 296: ...A32 HIOKI PQ3198A961 03...
Страница 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Страница 300: ...Index Index 4 HIOKI PQ3198A961 03...
Страница 301: ...HIOKI PQ3198A961 03...
Страница 302: ...HIOKI PQ3198A961 03...
Страница 303: ...HIOKI PQ3198A961 03...
Страница 304: ...www hioki com HIOKI PQ3198A961 03...