13.2 Input Specifications/Output Specifications/Measurement Specifications
198
Event OUT
Start of approx. 200 ms aggregation in which no transient overvoltage was detected for any channel
in the transient event IN state. The transient period (difference between the IN and OUT times) is
indicated.
Multiple-phase system treat-
ment
Begins when a transient is detected for any one of the U1 to U4 channels and ends when no tran-
sient is detected for any of the channels.
Saved waveforms
Event waveforms, Transient waveforms
Waveforms are saved for 2 ms before and after the position at which the transient overvoltage wave-
form was detected for the first transient IN and 2 ms before and after the point at which the transient
maximum voltage waveform was detected between the IN and OUT points.
(1) Transient overvoltage (Tran)
(2) Frequency cycle (Freq_wav)
Measurement method
Reciprocal method
Calculated as the reciprocal of the accumulated whole-cycle time during one U1 (reference chan-
nel) cycle.
Frequency is given per waveform.
When set to a measurement frequency of 400 Hz, calculated as the reciprocal of the accumulated
whole-cycle time during 8 cycles.
Average frequency is given for 8 waveforms.
Displayed item
Worst frequency cycle value between EVENT IN and EVENT OUT (max. deviation).
Measurement range
When the measurement frequency is set to 50 Hz/60 Hz :70.000 Hz
When the measurement frequency is set to 400 Hz
: 440.00 Hz
Measurement accuracy
When the measurement frequency is set to 50 Hz/60 Hz:
±
0.200 Hz or less (for input from 10% f.s. to 110% f.s.)
When the measurement frequency is set to 400 Hz:
±
2.00 Hz or less (for input from 10% f.s. to 110% f.s.)
Event threshold
Specified as deviation of 0.1 Hz to 9.9 Hz in 0.1 Hz increments.
Event IN
The time when the waveform exceeded the positive threshold or fallen below the negative thresh-
old for the first time
Event OUT
The time when the waveform returned to the range between the negative threshold plus 0.1 Hz
and the positive threshold minus 0.1 Hz
Note: Equivalent to 0.1 Hz frequency hysteresis.
Multiple-phase system treatment
None
Saved waveforms
Event waveforms
(3) RMS voltage refreshed each half-cycle (Urms1/2)
Measurement method
True RMS type, compliant with IEC61000-4-30
When the measurement frequency is set to 50 Hz/60 Hz, RMS voltage values are calculated using
sample data for 1 waveform derived by overlapping the voltage waveform every half-cycle. When
the measurement frequency is set to 400 Hz, the RMS voltage value is calculated for each voltage
waveform. The line voltage is used for 3-phase 3-wire (3P3W3M) connections, while the phase
voltage is used for 3-phase 4-wire connections.
Displayed item
RMS voltage refreshed each half-cycle
Measurement range
600.00 V
Measurement accuracy
When the measurement frequency is set to 50 Hz/60 Hz:
With 10 V to 660 V input:
Specified as 0.2% of nominal voltage with a nominal input voltage (Udin) of at least 100 V.
With input outside the range of 10 V to 660 V or a nominal input voltage (Udin) of less than 100 V:
±0.2% rdg. ±0.08% f.s.
When the measurement frequency is set to 400 Hz:
±
0.4% rdg.
±
0.50% f.s.
Event threshold
See the Dip, Swell, and Interruption sections.
Event IN
See the Dip, Swell, and Interruption sections.
Event OUT
See the Dip, Swell, and Interruption sections.
HIOKI PQ3198A961-03
Содержание PQ3198
Страница 2: ...HIOKI PQ3198A961 03...
Страница 6: ...Contents iv HIOKI PQ3198A961 03...
Страница 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Страница 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Страница 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Страница 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Страница 116: ...6 4 Displaying Harmonics 110 Holding the display Hold Measured values and waveforms will be held HIOKI PQ3198A961 03...
Страница 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Страница 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Страница 296: ...A32 HIOKI PQ3198A961 03...
Страница 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Страница 300: ...Index Index 4 HIOKI PQ3198A961 03...
Страница 301: ...HIOKI PQ3198A961 03...
Страница 302: ...HIOKI PQ3198A961 03...
Страница 303: ...HIOKI PQ3198A961 03...
Страница 304: ...www hioki com HIOKI PQ3198A961 03...