13.2 Input Specifications/Output Specifications/Measurement Specifications
205
10
13
Cha
p
ter 13 Spe
cificatio
ns
(18) Active power (P)
Measurement method
Measured every 10 cycles (50 Hz) or 12 cycles (60 Hz) (approx. 200 ms).
During 400 Hz measurement, measured every 80 cycles using the 8-cycle waveform (approx. 200
ms).
Displayed item
Active power for each channel and sum value for multiple channels
(for more information, see "13.8 Calculation Formula" (p.232))
Sink (consumption)
: Unsigned
Source (regeneration) : Negative
Measurement range
Combination of voltage × current range (see "13.9 Range Breakdown and Combination Accuracy"
(p.245))
Measurement accuracy
DC: ±0.5% rdg. ±0.5% f.s. + current sensor accuracy (defined for CH4 only)
AC:
When the measurement frequency is set to 50 Hz/60 Hz:
±
0.2% rdg.
±
0.1% f.s. + current sensor accuracy (The sum value is the total value for channels be-
ing used.)
When the measurement frequency is set to 400 Hz:
±
0.4% rdg.
±
0.6% f.s. +current sensor accuracy (The sum value is the total value for channels be-
ing used.)
Effects of power factor
1.0% rdg. or less (with power factor of 0.5)
Phase difference between internal circuit voltage and current: ±0.2865°
Event threshold
Comparison of power range absolute values
Event IN
Start of approx. 200 ms aggregation in which the absolute value was greater than the threshold
Event OUT
Start of approx. 200 ms aggregation in which the reading was less than (threshold - hysteresis)
following the EVENT IN state
Multiple-phase system treatment
Separate by channel
Saved waveforms
Event waveforms
(19) Efficiency (Eff)
Measurement method
Calculated based on the ratio of channels' respective active power values
(For more information, see "13.8 Calculation Formula" (p.232))
Displayed item
Eff1, Eff2
Measurement range
0.00 to 200.00[%]
Measurement accuracy
±
1 dgt. for calculations derived from the various measurement values.
Event threshold
N/A
HIOKI PQ3198A961-03
Содержание PQ3198
Страница 2: ...HIOKI PQ3198A961 03...
Страница 6: ...Contents iv HIOKI PQ3198A961 03...
Страница 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Страница 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Страница 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Страница 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Страница 116: ...6 4 Displaying Harmonics 110 Holding the display Hold Measured values and waveforms will be held HIOKI PQ3198A961 03...
Страница 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Страница 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Страница 296: ...A32 HIOKI PQ3198A961 03...
Страница 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Страница 300: ...Index Index 4 HIOKI PQ3198A961 03...
Страница 301: ...HIOKI PQ3198A961 03...
Страница 302: ...HIOKI PQ3198A961 03...
Страница 303: ...HIOKI PQ3198A961 03...
Страница 304: ...www hioki com HIOKI PQ3198A961 03...