8
An all pole, separate disconnect switch, with proper capacity
fuses or breakers must be installed at a convenient location
between the fryer and the power source, and must be installed
according to national and local codes. It should be an insulated
copper conductor rated for 600 volts and 90° C. For runs
longer than 50 feet (15.24 m), use the next larger wire size. CE
units require a minimum wire size of 6 mm to be wired to the
terminal block.
It is recommended that a 30 mA rated protective device such
as a residual current circuit breaker (RCCB), or ground fault
circuit interrupter (GFCI), be used on the fryer circuit.
Permanently connected electric fryers with casters must be
installed with flexible conduit and a cable restraint, when in
-
stalled in the United States. See illustration at left. Holes are
available in the rear fryer frame for securing the cable restraint
to the fryer. The cable restraint does not prevent the fryer from
tipping.
Each vat has it’s own power cord assembly, and uses the choic-
es of plugs below, depending upon voltage option and location
of fryer.
The supply power cords shall be oil-resistant, sheathed flexible
cable, no lighter than ordinary polychloroprene or other equiva-
lent synthetic elastomer-sheathed cord.
2-6. ELECTRICAL
REQUIREMENTS
(Continued)
DRYWALL CONSTRUCTION
Secure I-bolt to a building stud. Do
not attach to drywall only. Preferred
installation is approximately six
inches to either side of service.
Cable restraint must be at least six
inches shorter than flexible conduit.
HP Part no: 16242
Hubbell no: HBL8451C
Plug 250V/NEMA 15-50P
HP Part no: 37514
Hubbell no: HBL8461C
Plug 250V/NEMA 15-60P
HP Part no: 21335
Hubbell Part no: HBL8452C
Plug 250V/NEMA 15-50P/Angle
HP Part no: 58146
Hubbell Part no: HBL8462C
Plug 250V/NEMA 15-60P/Angle
Aug. 2011