OPERATION
6
89
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
C4.1.7
Low Error
Current
This menu item is available if C4.1.5 Error
Function is set to "Low". You can change
the value to which the current output will
change if an error occurs.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
3.5...3.6 mA
3.5 mA
C4.1.8
High Error
Current
This menu item is available if C4.1.5 Error
Function is set to "High". You can change
the value to which the current output will
change if an error occurs.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
21.0...21.5 mA
21.5 mA
C4.1.9 Trimming
C4.1.9.2
4mA Trimming
Use this menu item if the current output of
the device is set to 4 mA, but the measured
loop current is not 4 mA. Enter the
measured value.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0.0...25.0 mA
4 mA
C4.1.9.5
20mA Trimming Use this menu item if the current output of
the device is set to 20 mA, but the
measured loop current is not 20 mA. Enter
the measured value.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0.0...25.0 mA
20 mA
C5 Communication
C5.1 HART
C5.1 HART
C5.1 HART
C5.1 HART
C5.1.1
Current Loop
Mode
Set this menu item to "On" if the "Primary
Variable" for current output 1 must also be
transmitted as a 4
…
20 mA signal. If this
menu item is set to "Off', this stops the
4
…
20 mA signal and starts HART
®
multi-
drop mode.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
On, Off
On
C5.1.2 Identification
C5.1.2.1
Polling Address A polling address more than 0 will start
HART
®
multi-drop mode. If you start
HART
®
multi-drop mode, the current
output stays constant at 4 mA.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Operator
000...063
0
C5.1.2.2
Tag
Use this menu item to change the Tag
name. It can have a maximum of 8
characters. For more data about the
characters available, refer to
Keypad
functions
on page 68 (values in menu
items).
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Operator
—
TANK01
Menu No. Function
Function description
Selection list
Default
www.hawkmeasurement.com
Содержание Senator S24S
Страница 173: ...NOTES 11 173 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Страница 174: ...11 NOTES 174 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Страница 175: ...NOTES 11 175 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...