OPERATION
6
87
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
C2.8
Empty
Spectrum
Enable
This function starts and stops the
interference signal filter. Interference
signals are the result of fixed and moving
obstacles inside the tank. If you must do a
spectrum analysis, record an empty
spectrum first. Do the "Empty Spectrum"
procedure (menu A4.2) in the Quick Setup
menu.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Disabled, Enabled
Disabled
C3 Conversion
C3.1 Edit Table
C3.1 Edit Table
C3.1 Edit Table
C3.1 Edit Table
C3.1.1
Erase Table?
Before you can make a conversion table,
you must delete the data that is stored in
the device at this time. If you set this menu
item to "No" you will go back to menu C3.1.
If you set it to "Yes", you will go to menu
item C3.1.3 Select Conversion.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Yes, No
No
C3.1.3
Select
Conversion
If you must make a volume conversion
table, set this menu item to "Volume". If
you must make a mass conversion table,
set this menu item to "Mass". If you must
make a linearization table to make sure
that the readings always agree with
reference measurements, set this menu
item to "Linearization".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Volume, Mass,
Linearization
Volume
C3.2 Input Table
C3.2 Input Table
C3.2 Input Table
C3.2 Input Table
C3.2.2
Point
This adds a point on the conversion table.
Each time you enter this menu item, this
number will automatically increment by 1
point. If it is necessary to change the data
for a point, change the point number. When
you push [
^
^
^
^
], you go to menu item C3.2.4
Level.
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Expert
min-max:
001...050
001
C3.2.4
Level
Enter the level value for the point given in
C3.2.2. Push [
^
^
^
^
] to confirm the level value
and go to C3.2.5 Conv. Value.
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Expert
min-max:
0.0...100.0
+03
mm /
0.0...3937.0
¨
0.0 mm / 0.0
¨
C3.2.5
Conv. Value
Enter the conversion value (volume, mass
or linearization) for the point given in
C3.2.2. Push [
^
^
^
^
] to confirm the conversion
value and go back to menu C3.2.
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Minimum access level to do the procedure:
Expert
min-max:
Volume:
0.0...100.0
+09
m
³
/
0.0...26.417
+12
gal
Mass:
0.0...100.0
+09
kg /
0.0...220.46
+09
lb
Linearization:
0.0...100.0
+12
mm /
0.0...3.937
+12
¨
Volume:
0.0 m
³
/ 0.0 gal
Mass:
0.0 kg / 0.0 lb
Linearization:
0.0 mm / 0.0
¨
Menu No. Function
Function description
Selection list
Default
www.hawkmeasurement.com