6
OPERATION
88
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
C4 Output
C4.1 Current Output 1
C4.1 Current Output 1
C4.1 Current Output 1
C4.1 Current Output 1
C4.1.1
Current Out. 1
Var.
Make a selection from the available output
functions to scale the current output
values. This is not shown in the Normal
mode.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Level, Distance, Sensor
Value, Reflection
2
Level
1
C4.1.2
0% Range
Give a measurement value to 0% output
(refer also to menu item C4.1.1 Current
C4.1.1 Current
C4.1.1 Current
C4.1.1 Current
Out. 1 Var
Out. 1 Var
Out. 1 Var
Out. 1 Var for the output function). 0%
output = 4 mA. It is possible to have an
output less than 4 mA (<0%) if you set
C4.1.4 Current Out. Range to "3.8-
20.5 mA".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
-4.9
+06
...+5.1
+06
mm /
-192.91
+03
...+200.79
+03
/
-16076...+16732 ft
0.0 mm
1
C4.1.3
100% Range
Give a measurement value to 100% output
(refer also to menu item C4.1.1 Current
C4.1.1 Current
C4.1.1 Current
C4.1.1 Current
Out. 1 Var
Out. 1 Var
Out. 1 Var
Out. 1 Var for the output function). 100%
output = 20 mA. It is possible to have an
output more than 20 mA (>100%) if you set
C4.1.4 Current Out. Range to "3.8-
20.5 mA".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
-4.9
+06
...+5.1
+06
mm /
-192.91
+03
...+200.79
+03
/
-16076...+16732 ft
C1.2 Tank
Height - C1.5
Blocking
Distance
1
C4.1.4
Current Out.
Range
This menu item sets the limits of the output
current range to 1 of 4 available options:
standard limits (4...20 mA), NAMUR NE 43-
compliant limits (3.8...20.5 mA), reversed
standard limits and reversed NAMUR NE
43-compliant limits. You use standard
limits when you want the 0% output to be
4 mA and the 100% output to be 20 mA. You
use reversed limits when you want the 0%
output to be to be 20 mA and 100% output
to be 4 mA.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
4-20 mA, 3.8-20.5 mA
(NAMUR), 4-20 mA
(reversed), 3.8-20.5 mA
(reversed)
4-20 mA
1
C4.1.5
Error Function
This sets the behaviour of current output 1
if an error occurs. If this menu item is set to
"Off", no signal is given (this parameter is
not available if menu item C4.1.4 is set to
"3.8-20.5 mA" (NAMUR) or "3.8-20.5 mA
(reversed)"). If this menu item is set to
"Hold", the output current stays at the
value where the error occurred (this
parameter is not available if menu item
C4.1.4 is set to "3.8-20.5 mA" (NAMUR) or
"3.8-20.5 mA (reversed)"). If this menu item
is set to "Low", the output current changes
to 3.5 mA (default value) if an error occurs.
If this menu item is set to "High", the output
current changes to 21.5 mA (default value)
if an error occurs. You can change the low
error current value in menu item C4.1.7.
You can change the high error current
value in menu item C4.1.8.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Off, Low, High, Hold
Hold
1
Menu No. Function
Function description
Selection list